25 | On 03/24/2023, at 2:24 PM, Licensing Program Analyst (LPA) Veronica Martinez Garza conducted an unannounced case management inspection for an Action Level Exceedance (ALE) detected in the water fixture in the facility. LPA met with facility director Brittany Shafferman, during the visit. There were 0-day care children present. A COVID 19 risk assessment was conducted prior to entering the facility.
Analyst reviewed new Assembly Bill (AB) 2370, Chapter 676, Statutes of 2018, which requires the testing of water for lead in Child Care Centers (CCCs) with facility director during the inspection. Per AB 2370, all CCCs that are located in buildings constructed before January 1, 2010, must have their water tested and post the results by January 1, 2023, and every 5 years after the date of the first testing.
Facility provided facility sketch and required forms LIC 9276, LIC999 and LIC9275 to LPA on 03/08/23. On 02/28/2023, the Department received notification from the State Water Resources Control Board (SWRCB), Division of Drinking Water (DDW). The SWRCB report indicated the facility was inspected and samples were collected on 02/11/2023. Faucets and drinking fountains reported with 5.5 ppb or greater lead
exceedance levels were as follows:
A – Sink Faucet in Sunroom Classroom (9.200 UG/L) – Faucet used only for hand washing
C – Sink Faucet in Sunroom Classroom (12.000 UG/L) – Faucet used only for hand washing
D – Sink Faucet in Sunroom Classroom (11.000 UG/L) – Faucet used only for hand washing
G – Sink Faucet in Greenhouse Classroom (7.900 UG/L) – Faucet used only for hand washing
I – Sink Faucet in Crib Classroom (9.900 UG/L) – Faucet used only for hand washing
J – Play yard Water Fountain (5.600 UG/L) – Faucet is currently not in use
K –Treehouse Sink Faucet Classroom (9.300 UG/L) – Faucet used only for hand washing
L – Water Fountain across from Treehouse Classroom (22.000 UG/L) – Faucet is currently not in use
Page 1 of 2 |