1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25 | Licensing Program Analyst (LPA) Michael Cava conducted an Annual Required visit and inspection of the facility. LPA met with the assistant administrator, Clyde Acabal and explained the reason for the visit.
At 09:25am, with the assistance of staff, LPA took a tour of the physical plant. The facility is a one story building that houses level 4C elderly clients. Required postings were observed in the entry area. The smoke alarms are hard wired and battery operated. Pull chord to alert the fire department is also active. The carbon monoxide detector is located in between rooms #1 and #2. There are two (2) fire extinguishers, located in the kitchen and lounge. The last fire drill was held on 05/08/24 and the last earthquake drill on 04/05/24.
Kitchen: The kitchen appliances and fixtures were functional. LPA found a sufficient amount of perishable and non-perishable food sealed and properly stored. Knives and cleaning supplies were locked and inaccessible during the visit.
Bedrooms: The facility has six (6) bedrooms. Rooms #1 and #3 are private. Rooms #5 and #6 are shared. Rooms #2 and #4 are reserved for staff. The bedrooms designated for resident use were observed to be properly furnished with appropriate beddings and linens with sufficient lighting.
Bathrooms: There are four (4) bathrooms designated for both resident and staff use. Bathrooms were properly supplied and had functional fixtures. Hot water temperature was measured between 108 and 111 degrees Fahrenheit. No cleaning supplies were observed in any of the bathrooms
Common Areas: These included the living room, lounge and dining area. The living room is furnished with two couches, chair and tv. The dining room table is large enough to seat six individuals. The lounge is located by rooms #4 and #5. The lounge had two couches and a tv. Floors were mopped and clean. Exits and passageways were clear of obstruction. |